Service Hotline:400-688-3551
Home » News Center » Frequently Asked Questions » Installation requirements for high efficiency air filter of DC FFU fan filter unit in clean room workshop

Installation requirements for high efficiency air filter of DC FFU fan filter unit in clean room workshop

Views:0     Author:Site Editor     Publish Time: 2020-08-13      Origin:Site

1. High efficiency filter installation conditions

Before installing the high-efficiency filter, the clean room must be thoroughly cleaned and wiped. If there is dust in the purifying air conditioning system, it should be cleaned and wiped again to meet the cleaning requirements. If a high-efficiency filter is installed in the technical mezzanine or suspended ceiling, the technical mezzanine or suspended ceiling should also be thoroughly cleaned and wiped.

The clean room must be airtight during installation,DC FFUAfter the installation is completed and the operation is started, the clean air conditioner must be tested and run continuously for more than 12 hours, and the high efficiency filter shall be installed immediately after cleaning and wiping the clean room again.

The clean room is kept clean and free of dust. All keels have been installed and leveled.

The installer must be equipped with clean clothes and clean gloves to prevent man-made pollution of the box and filter.

In order to ensure the long-term and effective work of the high efficiency filter, the installation environment should not be in the oily, dusty, and humid air. Try to avoid contact with water or other corrosive liquids, so as not to affect its use effect.

It is recommended that the number of installers in each group is 6 people.

Article cover 566-378


2. Precautions for unloading and handling of DC FFU and HEPA filter

1. Shandong snyli PurificationDC FFUAnd the high-efficiency filter has been multi-protected packaging before leaving the factory. Please use a forklift to unload the entire pallet when unloading. Unloading should prevent the goods from dumping and avoid severe vibration and collision.

After unloading, the equipment should be placed in a dry, ventilated room for temporary storage. If it can only be stored outdoors, it should be covered with a tarp to avoid rain.

2. Since the high-efficiency filter uses ultra-fine glass fiber filter paper, the filter material is easily broken and damaged, causing particle leakage. Therefore, do not dump or crush the filter during unpacking and transportation to prevent severe vibration and collision.

Error: No dumping and transportation

When taking out the high-efficiency filter, it is prohibited to use a knife or sharp object to cut the packaging bag to avoid scratching the filter paper

Error: It is forbidden to cut the bag with a knife

Each piece of high-efficiency filter should be carried by two people. The operator must wear gloves. The process must be handled with care. Hold the filter frame with both hands. It is forbidden to hold the filter protection net, sharp objects to contact the filter paper, and no twisting filter.

Correct: Hold the filter frame with both hands

Error: Distortion filter is prohibited

Error: No one is allowed to carry the filter

3. The filters should not be placed in stacks, they should be horizontally ordered, and placed neatly against the wall in the installation waiting for installation. As shown below:

Correct: the filter is neatly placed

Error: prohibit filter stack extrusion

Three. Precautions for installation of high efficiency filter

Before installing the high-efficiency filter, the appearance of the filter must be inspected, including whether the filter paper, gasket, frame are damaged, whether the size and technical performance meet the design requirements, the appearance or the filter paper is severely damaged and the filter should be installed. Take pictures and reflect to the manufacturer for processing.

When installing, only hold the filter frame, handle it gently. To prevent severe vibration and collision, it is strictly forbidden for the installer to touch the filter paper inside the filter with fingers or other tools.

Error: It is forbidden to hold the filter protection net by hand

Pay attention to the direction when installing the filter, so that the arrow on the filter frame is outward, that is, the arrow on the outer frame should be consistent with the direction of the airflow.

Note: label airflow direction

Do not step on the filter protection net during installation, and it is forbidden to discard debris on the surface of the filter. Do not step on the filter protection net.

Error: Discarding debris on the filter is prohibited

Note: Do not step on the filter protection net

Other installation precautions: you must wear gloves, and be careful of cuts on your fingers.DC FFU The installation should be aligned with the filter. The edge of the FFU box should not be pressed on the filter. It is forbidden to cover the FFU; it is forbidden to step on the FFU air inlet ring.

Error: FFU and filter misaligned

Error: It is forbidden to cover items on FFU

Note: It is forbidden to step on the FFU inlet ring


Website:www.snyli.com               Mobile: 13355281100
Service Hotline: 400-688-3551    Mailbox:sales@snyli.com
Telephone: 0533-6217678
Factory Address: No. 16 Heilongjiang Road, Economic Development Zone, Liaocheng City, Shandong Province
Factory Address: West End of Weisi Road, Linzi District, Zibo City, Shandong Province
Copyrigh ©2019 Shandong Snyli [Snyli Environmental Technology (Shandong) Co., Ltd., Shandong Snyli Purification Technology Co., Ltd.] All Rights Reserved.
Lu ICP No. 16035622-1  Technical Support:Yi Qilai